Do farms need an SPCC plan?

Short answer

Only larger farms. Under the Water Resources Reform and Development Act (as amended in 2016), a farm with less than 2,500 gallons of aggregate aboveground oil storage doesn't need an SPCC plan, and neither does a farm with more than 2,500 but less than 6,000 gallons and no reportable discharge history. Above that, a plan is required, and farms with more than 6,000 but less than 20,000 gallons, no tank over 10,000 gallons and a clean history can self-certify it.

Farms were pulled into the SPCC rule like any other facility until Congress stepped in. Section 1049 of the Water Resources Reform and Development Act of 2014 (WRRDA), later amended, raised the thresholds for farms and loosened who can self-certify. EPA's WRRDA fact sheet lays out how it works. EPA still hasn't finished the rulemaking to write these numbers into 40 CFR 112, so the fact sheet is the place to check.

Is it a "farm"?

Under 40 CFR 112.2, a farm is a facility on a tract of land devoted to producing crops or raising animals, including fish, that produced and sold, or normally would have produced and sold, $1,000 or more of agricultural products in a year. That's a low bar; most working farms and ranches qualify.

The farm thresholds

Aggregate aboveground capacityReportable discharge history?Result
Less than 2,500 galDoesn't matterNo SPCC plan required
More than 2,500 but less than 6,000 galNoNo SPCC plan required
More than 2,500 but less than 6,000 galYesPlan required, certified by a PE
More than 6,000 but less than 20,000 gal, no tank over 10,000 galNoPlan required; the farmer can self-certify
20,000 gal or more, or any tank over 10,000 galEitherPlan required, certified by a PE

"Reportable discharge history" means one spill to water of more than 1,000 gallons, or two spills to water of more than 42 gallons each within any 12 months, in the three years before you certify the plan (or since becoming subject, if newer). EPA notes the 6,000-gallon figure may be adjusted after its study, to somewhere between 2,500 and 6,000 gallons. The farm also has to meet the rest of the SPCC test: it handles oil and a spill could reasonably reach water.

What a farm doesn't count

Example

A grain farm has a 4,000-gallon diesel tank and a 1,000-gallon gasoline tank at the shop, a 500-gallon diesel tank at a field on a separate parcel, 300 gallons of hydraulic and engine oil in 55-gallon drums, and a 275-gallon heating oil tank at the house. Counted: 4,000 + 1,000 + 300 = 5,300 gallons. The field tank (separate parcel, 1,000 gallons or less) and the house tank are left out. With no reportable spills, this farm doesn't need an SPCC plan. Add a second 1,000-gallon tank at the shop and it's at 6,300 gallons: it needs a plan, and it can self-certify.

Self-certifying on a farm

If your farm qualifies to self-certify, EPA publishes a free Tier I template (Appendix G to Part 112) and a farm-based example plan on its SPCC for Agriculture page. The template is limited to facilities with no container over 5,000 gallons; a farm with a larger tank prepares a full self-certified plan instead. See how self-certification works.

EPA's Oil Information Center answers SPCC questions at (800) 424-9346.

Related questions

Do tanks on separate fields count?

Not small ones. Under WRRDA, a farm container of 1,000 gallons or less on a separate parcel from the farm's other containers doesn't count toward the farm's aggregate capacity.

Does a tractor's fuel tank count?

No. A vehicle's own fuel tank is a motive power container and is excluded (40 CFR 112.1(d)(2)(ii)(B) and (d)(7)). Pesticide application equipment and mix containers are excluded too (112.1(d)(10)).

Find out where you stand, free

SpillPlan's free check tells you whether the SPCC rule applies, whether you can self-certify, how big your containment needs to be and what to inspect. If you need a Professional Engineer, it says so. The full plan kit is $549 if you want it.

Start the free check

Next questions