Tier I vs Tier II qualified facilities under the SPCC rule

Short answer

A qualified facility has 10,000 gallons or less of aboveground oil storage and no disqualifying spills in the past three years, so the owner can self-certify the SPCC plan. It's Tier I if no single aboveground container is over 5,000 gallons, and Tier II if any container is over 5,000 gallons (40 CFR 112.3(g)).

A Tier II qualified facility can prepare and self-certify its own SPCC plan instead of hiring a Professional Engineer. The test is in 40 CFR 112.3(g). Here it is step by step, with what counts and what doesn't.

The test

  1. Aggregate aboveground oil storage capacity of 10,000 U.S. gallons or less (§ 112.3(g)(2)).
  2. Clean discharge history: in the three years before you self-certify (or since becoming subject, if newer), no single discharge to navigable waters or shorelines over 1,000 gallons, and no two discharges over 42 gallons each within any 12-month period. Discharges caused by natural disasters, acts of war or terrorism don't count.
  3. Tier I or Tier II: if no individual aboveground container is over 5,000 gallons, you're Tier I (§ 112.3(g)(1)). If any container is over 5,000 gallons, you're Tier II.

What counts toward the aggregate

Worked examples

FacilityCounted capacityLargestResult
Contractor yard: 6,000-gal diesel AST, 1,000-gal double-wall gasoline, 8 drums, 2 totes, 300-gal used oil, 500-gal fuel trailer, 120-gal hydraulic system8,910 gal6,000 galTier II
Fleet shop: two 2,000-gal diesel tanks, 500-gal used oil, 10 drums5,050 gal2,000 galTier I
Fuel dealer: two 8,000-gal tanks16,000 gal8,000 galPE-certified plan required

Assumes a spill could reach water and no disqualifying discharges. The first row is the sample facility in our test kit.

Tier I vs Tier II at a glance

Tier ITier II
Aggregate aboveground capacity10,000 gal or less10,000 gal or less
Largest single aboveground container5,000 gal or lessAny container over 5,000 gal
Discharge history (3 years)No single discharge to water over 1,000 gal, and no two over 42 gal each within 12 months
Plan formatEPA's Appendix G template, or a plan meeting § 112.6(b) (§ 112.6(a)(1))A full plan meeting § 112.7 and subpart B or C (§ 112.6(b)(3))
Failure analysisDirection and quantity of a spill (§ 112.6(a)(3)(i))Direction, rate of flow and quantity (§ 112.7(b))
Overfill preventionA system or documented procedure for each container, regularly tested (§ 112.6(a)(3)(iii))At least one of the devices in § 112.8(c)(8), such as a high-level alarm or pump cutoff
Who certifiesThe owner or operator, with the eight statements in § 112.6(a)(1) or (b)(1). A PE must certify any environmental-equivalence alternative or impracticability determination (§ 112.6(b)(3)–(4)); the Appendix G template can't include them at all.
If the facility growsA container over 5,000 gal: move to a Tier II plan within 6 months; over 10,000 gal aggregate: PE plan (§ 112.6(a)(2))Over 10,000 gal aggregate: PE-certified plan within 6 months (§ 112.6(b)(2)(ii))

Most of the day-to-day obligations, such as containment sized for the largest container plus rain, inspections with signed records, annual briefings and the five-year review, are the same for both tiers.

Farms

Farms have their own thresholds under the Water Resources Reform and Development Act of 2014: a farm with more than 6,000 but less than 20,000 gallons, no tank over 10,000 gallons and no reportable discharge history may self-certify, and farm containers of 1,000 gallons or less on separate parcels don't count. Check EPA's farm fact sheet for current thresholds.