Does a 1,000-gallon tank need an SPCC plan?
Short answer
Not by itself. A single 1,000-gallon aboveground tank is below the 1,320-gallon threshold, so if it's the only oil container of 55 gallons or more at the facility, the federal SPCC rule doesn't apply. But it adds up fast: six 55-gallon drums (330 gallons) alongside it puts the facility at 1,330 gallons and over the line.
A 1,000-gallon aboveground tank is one of the most common setups on farms, ranches, contractor yards and small fleets, and it sits just under the federal line. Whether you need a plan depends on what else is on the property.
Why 1,000 gallons alone is exempt
The SPCC rule doesn't apply to a facility whose aggregate aboveground oil storage capacity is 1,320 U.S. gallons or less, counting only containers of 55 gallons or more (40 CFR 112.1(d)(2)(ii)), as long as completely buried storage is 42,000 gallons or less. One 1,000-gallon tank is 320 gallons under. Capacity means the tank's shell size (§ 112.2), so a 1,000-gallon tank counts as 1,000 even if you never fill it past 800.
How little it takes to cross 1,320
| Added to the 1,000-gal tank | New total | Plan needed?* |
|---|---|---|
| Five 55-gal drums (275 gal) | 1,275 gal | No |
| Six 55-gal drums (330 gal) | 1,330 gal | Yes |
| One 330-gal tote of hydraulic oil | 1,330 gal | Yes |
| A 500-gal gasoline tank | 1,500 gal | Yes |
| A standby generator with a 400-gal base tank | 1,400 gal | Yes |
| A pickup with a 100-gal transfer tank in the bed, used to fuel equipment | 1,100 gal | No, but see below |
| Thirty 5-gal pails of grease and oil | 1,000 gal | No (containers under 55 gal don't count) |
*Assuming the facility isn't a farm and a spill could reasonably reach water. Farms have higher thresholds.
A transfer tank that carries fuel for distribution to other equipment isn't a motive power container (the definition in § 112.2 excludes onboard containers used to store or transfer oil for further distribution), so it counts if it's 55 gallons or more.
If it's on a farm
Farms have their own thresholds under the Water Resources Reform and Development Act: a farm with less than 2,500 gallons of aggregate aboveground storage doesn't need a plan, and farm containers of 1,000 gallons or less on a separate parcel don't count toward the farm's total. A 1,000-gallon tank on a farm is very unlikely to trigger the rule on its own. Details are in Do farms need an SPCC plan?
Even if you're exempt
Being under the federal threshold doesn't make a spill legal. If oil from your tank reaches water and causes a sheen, you still have to report it to the National Response Center (40 CFR 110.6), and your state may have its own tank rules. Putting the tank on a containment pad or using a double-wall tank is cheap insurance either way.
Find out where you stand, free
SpillPlan's free check tells you whether the SPCC rule applies, whether you can self-certify, how big your containment needs to be and what to inspect. If you need a Professional Engineer, it says so. The full plan kit is $549 if you want it.
Next questions
- How many gallons of oil require an SPCC plan?
- Do farms need an SPCC plan?
- Do generators and belly tanks count toward the SPCC threshold?
- Do I need an SPCC plan?