What is the 110% secondary containment rule?
Short answer
The SPCC rule doesn't actually say 110%. It requires secondary containment for the entire capacity of the largest single container plus sufficient freeboard for precipitation (40 CFR 112.8(c)(2)). EPA's inspector guidance calls 110% of the largest tank an acceptable rule of thumb in many situations, but recommends sizing freeboard for a 25-year, 24-hour storm, which can be more.
"110%" is so widely repeated that many people assume it's written into the SPCC rule. It isn't. Here is what the rule actually requires, where 110% comes from, and how to check whether your containment is big enough.
What the rule says
For bulk storage containers at onshore facilities, 40 CFR 112.8(c)(2) requires "a secondary means of containment for the entire capacity of the largest single container and sufficient freeboard to contain precipitation," and diked areas "sufficiently impervious to contain discharged oil." Section 112.8(c)(11) sets the same sizing for mobile or portable containers such as drums and totes. Self-certified Tier I plans follow nearly identical wording in § 112.6(a)(3)(ii).
The rule doesn't define "sufficient freeboard." EPA's SPCC Guidance for Regional Inspectors (ch. 4) explains that EPA considers precipitation from a 25-year, 24-hour storm the proper standard, but chose not to make it enforceable. It then says a 110% rule of thumb "may be an acceptable design criterion in many situations," while warning that in some places 110% won't hold the rain from a real storm. Many state tank rules do require 110%.
Two kinds of containment
| General containment | Sized containment | |
|---|---|---|
| Rule | § 112.7(c) | § 112.8(c)(2) and (c)(11) |
| Applies to | All oil containers, equipment, piping and transfer areas | Bulk storage containers, including drums and totes (not mobile refuelers) |
| Size | Typical failure mode and most likely quantity spilled | Largest container plus freeboard for precipitation |
| Examples | Sorbents, drip pans, curbing, spill kits at a fill point | Concrete or steel dikes, containment basins, double-wall tanks, spill pallets of the right size |
Worked example: checking a dike
A concrete dike is 12 ft by 10 ft with walls 2 ft high. Inside are a 1,000-gallon horizontal diesel tank and a 500-gallon vertical tank 4 ft in diameter. The facility uses a 25-year, 24-hour rainfall of 5 inches (an example; look up your own on NOAA's Atlas 14 server).
| Step | Calculation | Result |
|---|---|---|
| Gross dike volume | 12 × 10 × 2 = 240 ft³ × 7.48 gal/ft³ | 1,795 gal |
| Minus space taken by the other tank, up to the wall height | π × 2² × 2 = 25.1 ft³ × 7.48 | −188 gal |
| Net capacity | 1,607 gal | |
| Largest container | 1,000 gal | |
| Rain on the dike area | 120 ft² × (5 ÷ 12) ft = 50 ft³ × 7.48 | 374 gal |
| Needed (storm method) | 1,000 + 374 | 1,374 gal ✔ |
| Needed (110% rule of thumb) | 1,000 × 1.10 | 1,100 gal ✔ |
This dike passes both ways. Notice the storm method asks for more than 110% here: on a small dike in a wet climate, rain can be a big share of the volume. EPA's own example in ch. 4, a 20,000-gallon tank in a 45 × 20 ft dike, needs a 3.27 ft wall at 110% and 3.35 ft for a 4.5-inch storm. Also subtract any pads, supports or equipment inside the dike that take up space.
Practical points
- One dike can serve many containers. EPA says you don't need separate containment for each drum or tank; a shared area works if it meets each container's requirement.
- Keep rainwater out of the volume. Drain dikes with manually operated, normally closed valves, inspect the water before release, and keep records (§ 112.8(b)(1)–(2), (c)(3)). A dike half full of rainwater isn't containment.
- Impervious means impervious. Cracked concrete, gaps where pipes pass through walls, and gravel-floored berms are common inspection findings.
- If you can't build it, only a PE can certify an impracticability determination and the contingency plan that replaces containment (§ 112.7(d), § 112.6(b)(3)(ii)).
Related questions
Does each drum need its own containment?
No. EPA says separate containment for each container isn't required; a common containment area or drainage system can serve several drums or tanks, as long as each container's requirement is met (EPA, "Secondary containment for each container").
Do 5-gallon buckets require secondary containment?
Not under SPCC. Containers under 55 gallons are exempt from the rule (40 CFR 112.1(d)(5)), though other codes may apply.
What's the difference between general and sized containment?
General containment (112.7(c)) applies to all oil containers and equipment and only has to handle the typical failure and most likely spill. Sized containment (112.8(c)(2) and (c)(11)) applies to bulk storage containers and must hold the largest container plus precipitation.
Find out where you stand, free
SpillPlan's free check tells you whether the SPCC rule applies, whether you can self-certify, how big your containment needs to be and what to inspect. If you need a Professional Engineer, it says so. The full plan kit is $549 if you want it.
Next questions
- Does a double-walled tank count as secondary containment?
- Does oil-filled equipment need secondary containment under SPCC?
- What inspections does an SPCC plan require?
- Do generators and belly tanks count toward the SPCC threshold?
Sources
- 40 CFR 112.8 — Onshore facilities (excluding production): drainage, bulk storage, transfers
- 40 CFR 112.7 — General requirements for SPCC Plans
- 40 CFR 112.1 — General applicability (1,320-gallon and 55-gallon thresholds, exemptions)
- EPA SPCC Guidance for Regional Inspectors, ch. 4: Secondary containment and impracticability (2013)
- EPA — Specifications for bulk storage secondary containment (25-year, 24-hour storm)
- EPA — Secondary containment for each container under SPCC
- NOAA Atlas 14 Precipitation Frequency Data Server (25-year, 24-hour rainfall)