How many gallons of oil require an SPCC plan?
Short answer
More than 1,320 U.S. gallons of aggregate aboveground oil storage capacity, or more than 42,000 gallons in completely buried tanks. You add up the shell capacity of every container of 55 gallons or more, whether it's full or empty, and leave out the specific exclusions in 40 CFR 112.1(d)(2).
The threshold sounds simple, but almost every SPCC question we see comes down to what goes into the count. Three rules from 40 CFR 112.1 and 112.2 do most of the work.
The three counting rules
- Count capacity, not contents. "Storage capacity" means the shell capacity of the container (§ 112.2). A tank that's usually a quarter full still counts at its full size. So does an empty one in standby or seasonal use (§ 112.1(b)(3)).
- Only count containers of 55 gallons or more. Smaller containers are left out of the aggregate (§ 112.1(d)(2)(ii)) and are outside the rule altogether (§ 112.1(d)(5)). A shelf of 5-gallon pails doesn't count, whatever the total.
- Count every kind of oil container, not just fuel tanks: drums, totes, used-oil tanks, mobile tanks, generator fuel tanks, and oil-filled equipment like transformers and hydraulic reservoirs.
What you leave out
Section 112.1(d)(2)(ii) excludes these from the aboveground total:
- Permanently closed containers (emptied, disconnected and blanked off, valves locked, sign posted with the closure date)
- Motive power containers, meaning a vehicle's own fuel tank and its onboard oil-filled equipment
- Hot-mix asphalt and hot-mix asphalt containers
- Heating oil containers used solely at a single-family residence
- Pesticide application equipment and related mix containers
- Milk and milk product containers
Completely buried tanks that are subject to all of the federal UST technical requirements (40 CFR 280, or an approved state program) are excluded from the 42,000-gallon buried count and exempt from the SPCC rule (§ 112.1(d)(2)(i), (d)(4)).
Worked examples
| What's on site | Counted | Over 1,320? |
|---|---|---|
| 24 drums of lube oil (55 gal each) | 1,320 gal | No. Exactly 1,320 is "1,320 or less," which is exempt |
| 25 drums of lube oil | 1,375 gal | Yes |
| 1,000-gal diesel tank + two 275-gal totes of hydraulic oil | 1,550 gal | Yes |
| 1,000-gal diesel tank + forty 5-gal pails | 1,000 gal (pails don't count) | No |
| 500-gal used oil tank + 300-gal transformer + 600-gal generator base tank | 1,400 gal | Yes |
| Five pickup trucks with 36-gal tanks + a 1,000-gal fuel tank | 1,000 gal (vehicle tanks are motive power) | No |
Does everything count toward the self-certification limit too?
Yes. The same aggregate aboveground capacity is used for the 10,000-gallon qualified facility limit in § 112.3(g), so if you're over 1,320 gallons, the next number that matters is 10,000. See Tier I vs Tier II qualified facilities.
Farms are the main exception to these numbers. Congress set higher thresholds for them; see Do farms need an SPCC plan?
Related questions
Do I count how much oil is in the tank or how big it is?
How big it is. Storage capacity means the shell capacity of the container (40 CFR 112.2), so a half-full 1,000-gallon tank counts as 1,000 gallons.
Do 5-gallon pails and 30-gallon drums count?
No. Containers smaller than 55 gallons are not counted toward the threshold and are outside the rule (40 CFR 112.1(d)(2)(ii) and (d)(5)).
Find out where you stand, free
SpillPlan's free check tells you whether the SPCC rule applies, whether you can self-certify, how big your containment needs to be and what to inspect. If you need a Professional Engineer, it says so. The full plan kit is $549 if you want it.
Next questions
- Does a 1,000-gallon tank need an SPCC plan?
- What isn't covered by the SPCC rule?
- Do I need an SPCC plan?
- Does oil-filled equipment need secondary containment under SPCC?