What isn't covered by the SPCC rule?

Short answer

The SPCC rule doesn't cover containers under 55 gallons, a vehicle's own fuel tank (motive power containers), heating oil used only at a single-family home, hot-mix asphalt, pesticide application equipment, milk containers, permanently closed containers, wastewater-treatment-only equipment, or completely buried tanks that meet all the federal UST rules (40 CFR 112.1(d)). Facilities where a spill couldn't reach water, judged on geography alone, are outside the rule entirely.

Section 112.1(d) lists what the SPCC rule doesn't apply to. Some items are left out of the gallon count; others are outside the rule entirely. Here's the full list in plain English, with the conditions that matter.

Whole facilities that are outside the rule

Containers and equipment that are exempt

ExemptConditionRule
Containers under 55 gallonsAny oil§ 112.1(d)(5)
Motive power containersA vehicle's own fuel tank and onboard oil-filled equipment. Fueling them at a regulated facility is still covered.§ 112.1(d)(7)
Home heating oilUsed solely at a single-family residence§ 112.1(d)(9)
Hot-mix asphaltAnd hot-mix asphalt containers§ 112.1(d)(8)
Pesticide application equipmentAnd related mix containers§ 112.1(d)(10)
Milk and milk product containersAnd associated piping and appurtenances§ 112.1(d)(12)
Completely buried tanks under the UST rulesSubject to all technical requirements of 40 CFR 280 or an approved state program. Mark them "exempt" on the facility diagram if you have a plan.§ 112.1(d)(4)
Wastewater treatmentUsed exclusively for wastewater treatment and not to meet a Part 112 requirement. Oil recovery or recycling isn't wastewater treatment.§ 112.1(d)(6)
Intra-facility gathering linesSubject to DOT pipeline rules (49 CFR 192 or 195); mark as "exempt" on the diagram§ 112.1(d)(11)
Permanently closed containersExcluded from capacity once they meet the definition below§ 112.1(d)(2)

What "permanently closed" means

An empty tank isn't automatically out of the count. Under § 112.2 a container is permanently closed only when all liquid and sludge has been removed from it and its connecting lines, all lines are disconnected and blanked off, all valves except vents are closed and locked, and a conspicuous sign on the container says it's permanently closed and gives the closure date. Tanks kept for standby, seasonal or temporary use still count (§ 112.1(b)(3)).

EPA can still require a plan

Even if an exemption applies, the EPA Regional Administrator can require a plan after a written determination under § 112.1(f). That's rare, but it's why spills from exempt facilities still get attention.

Related questions

Do 5-gallon buckets require secondary containment?

Not under the SPCC rule. Containers smaller than 55 gallons are exempt (40 CFR 112.1(d)(5)). Fire codes, OSHA, hazardous-waste rules or your state may still have storage requirements for them.

Does an empty tank count?

Yes, unless it's permanently closed: all liquid and sludge removed, lines disconnected and blanked off, valves locked, and a sign posted with the closure date (40 CFR 112.2). An empty tank in standby or seasonal use still counts (112.1(b)(3)).

Find out where you stand, free

SpillPlan's free check tells you whether the SPCC rule applies, whether you can self-certify, how big your containment needs to be and what to inspect. If you need a Professional Engineer, it says so. The full plan kit is $549 if you want it.

Start the free check